Industrial modular Clean Room time:2022/11/24 08:25:27 click:166

Definition of air shower room: also known as air shower room, it is personnel or goods into the clean area by the fan through the air shower nozzle after efficient filtration of clean wind blowing dust adsorption on the surface of people or objects, a kind of local purification equipment with strong versatility. So when the air shower room failure, how to deal with it?

How to deal with the fault of the air shower room

The power switch is faulty. Usually there are four places in the air shower room to cut off the power supply: 1. The power switch of the outdoor box of the air shower; 2, the control panel of the air shower box; 3, on both sides of the air shower box (here the power switch can prevent the emergency to cut off the power supply, effectively improve the personal safety of the staff). When the power indicator light is not clear, do not prevent to check the above four air shower power supply.

The fan in the air shower room fails when not working. When the air shower room does not work, it is time to check whether the emergency switch of the outdoor box of the air shower is cut off. If it is cut off, gently press with your hand and rotate to the right to let go.

The air shower fan is inverted or the wind speed in the air shower is very small, please be sure to check whether the 380V three-phase four-wire line is reverse connected, general air shower manufacturers factory installation will have a special electrician to connect the line; If the line source of the air shower is reversed, the light will lead to the air shower fan does not work or reverse the wind speed of the air shower room is reduced, the heavy will burn the circuit board of the whole air shower room; It is recommended that the air shower enterprise do not lightly replace the wiring, because the production needs to determine to move, please consult the air shower manufacturer to solve.

The air shower room does not blow, in addition to the above three points, but also need to check the emergency stop key inside the air shower room is pressed, such as the emergency stop key for the color, the air shower room will not blow; To press the emergency stop button again can work normally.

Air shower room can not automatically induction blowing fault, please check the air shower room box in the lower right corner of the light sensing system, to see whether the light sensing device is installed correctly, such as the two sides of the light is opposite and the light sense is normal, you can automatically induction blowing.

When the air shower room is used for a period of time, the wind speed is very low. Please check whether the primary and high efficiency filter of the air shower room has too much dust. If so, please replace the filter. (The primary effect filter in the air shower room is generally replaced once within 1-6 months, and the high efficiency filter in the air shower room is generally replaced once within 6-12 months).